CN
YX-ZR-YJV
0.6/1kV Flame-Retardant Five-core YJV (Copper Core) YX-ZR-YJV
Main Functions: YX-ZR-YJV Flame-Retardant YJV (PVC Sheathing Power Cable with XLPE Insulation) LV-Series are used in rated voltage 0.6/1kV power transmission and distribution systems. BVR/ BV PVC Type Sheathing Power Cable are suitable for fixed laying of power plants with rated AC power of 450/750V and below.
0.6/1kV Flame-Retardant Five-core YJV (Copper Core) YX-ZR-YJV

Technical Parameter

Model Nominal cross sectional area of core
(mm2)
Insulation thickness
(mm)
Sheath thickness
(mm)
Approx. outside diameter of cable
(mm)
Approx. weight of cable Insulation resistance
(90℃)
(MΩ.km)
AC Testing voltage (KV/5min) Cable current carrying capacity
In Air Direct in ground
Cu
(kg/km)
Al
(kg/km)
    Cu
(A)
Al
(A)
Cu
(A)
Al
(A)
YX-ZR-YJV-5×25 5×25 0.9 1.8 26 1440 640 ≥0.444 3.5 100 75 140 90
YX-ZR-YJV-5×35 5×35 0.9 1.9 29 1930 830 ≥0.379 3.5 125 90 160 130
YX-ZR-YJV-5×50 5×50 1.0 2.0 33 2670 1140 ≥0.355 3.5 150 110 185 135
YX-ZR-YJV-5×70 5×70 1.1 2.2 38 3860 1560 ≥0.335 3.5 190 145 220 165
YX-ZR-YJV-5×95 5×95 1.1 2.3 43 4940 1960 ≥0.290 3.5 235 175 265 200
YX-ZR-YJV-5×120 5×120 1.2 2.5 48 6250 2450 ≥0.282 3.5 265 195 285 210
YX-ZR-YJV-5×150 5×150 1.4 2.7 53 7720 3120 ≥0.294 3.5 300 225 310 225
YX-ZR-YJV-5×185 5×185 1.6 2.9 60 9580 3740 ≥0.303 3.5 360 260 345 260
YX-ZR-YJV-5×240 5×240 1.7 3.1 67 12310 4740 ≥0.283 3.5 420 310 400 305
YX-ZR-YJV-4×25+1×16 4×25+1×16 0.9 1.8 25 1340 600 ≥0.444 3.5 100 75 140 90
YX-ZR-YJV-4×35+1×16 4×35+1×16 0.9 1.8 27 1730 740 ≥0.379 3.5 125 90 160 130
YX-ZR-YJV-4×50+1×25 4×50+1×25 1.0 2.0 31 2420 1020 ≥0.355 3.5 150 110 185 135
YX-ZR-YJV-4×70+1×35 4×70+1×35 1.1 2.1 36 3470 1400 ≥0.335 3.5 190 145 220 165
YX-ZR-YJV-4×95+1×50 4×95+1×50 1.1 2.3 41 4500 1800 ≥0.290 3.5 235 175 265 200
YX-ZR-YJV-4×120+1×70 4×120+1×70 1.2 2.4 46 5760 2270 ≥0.282 3.5 265 195 285 210
YX-ZR-YJV-4×150+1×70 4×150+1×70 1.4 2.6 50 6940 2730 ≥0.294 3.5 300 225 310 225
YX-ZR-YJV-4×185+1×95 4×185+1×95 1.6 2.8 56 8650 3390 ≥0.303 3.5 360 260 345 260
YX-ZR-YJV-4×240+1×120 4×240+1×120 1.7 3.0 63 11090 4280 ≥0.283 3.5 420 310 400 305
YX-ZR-YJV-3×25+2×16 3×25+2×16 0.9 1.8 24 1240 570 ≥0.444 3.5 100 75 140 90
YX-ZR-YJV-3×35+2×16 3×35+2×16 0.9 1.8 26 1540 670 ≥0.379 3.5 125 90 160 130
YX-ZR-YJV-3×50+2×25 3×50+2×25 1.0 1.9 30 2170 920 ≥0.355 3.5 150 110 185 135
YX-ZR-YJV-3×70+2×35 3×70+2×35 1.1 2.1 34 3090 1270 ≥0.335 3.5 190 145 220 165
YX-ZR-YJV-3×95+2×50 3×95+2×50 1.1 2.2 39 4030 1610 ≥0.290 3.5 235 175 265 200
YX-ZR-YJV-3×120+2×70 3×120+2×70 1.2 2.4 44 5290 1840 ≥0.282 3.5 265 195 285 210
YX-ZR-YJV-3×150+2×70 3×150+2×70 1.4 2.5 47 6170 2440 ≥0.294 3.5 300 225 310 225
YX-ZR-YJV-3×185+2×95 3×185+2×95 1.6 2.7 53 6870 2770 ≥0.303 3.5 360 260 345 260
YX-ZR-YJV-3×240+2×120 3×240+2×120 1.7 2.9 59 9880 3820 ≥0.283 3.5 420 310 400 305

Main Functions

YX-ZR-YJV Flame-Retardant YJV (PVC Sheathing Power Cable with XLPE Insulation) LV-Series are used in rated voltage 0.6/1kV power transmission and distribution systems. BVR/ BV PVC Type Sheathing Power Cable are suitable for fixed laying of power plants with rated AC power of 450/750V and below.
 

Copyright © Zhejiang Yongxin Electric Technology Co., Ltd 2013 All Rights Reserved 浙ICP备19040239号 Designed By: Eking